(T3464) AC Guarded Digital Output Module
P D - 6 0 2 1 M a r - 0 6
21
Load Current (maximum)
1 amp maximum per output
0
°
to 40
°
C, derated linearly
to 0.5 amp at 60
°
C
16 amps maximum per
module at 0
°
C, derated
linearly to 8 amps at 60
°
C
Load Current (minimum)
Guarded mode:
Fault tolerant mode:
50 mA
150 mA
Line Current
Load current plus 16 amps
transient during crowbar
actuation
Neutral Current
16 amps maximum transient
during crowbar actuation
On State Drop
1.6 V, maximum
Surge Current
10 amps for 20 msec
Output Leakage
Guarded mode:
Fault tolerant mode:
5 mA maximum at 60 Hz
10 mA maximum at 60 Hz
Fusing
One 2 A, 250 V, fast acting
(3AG) per output, front panel
mounted
Turn-On Delay
1 AC cycle maximum
Turn-Off Delay
1.5 AC cycle maximum
Over Voltage Protection
160 VAC, continuous
Load Bump
(Turn-on)
70 V peak for 1.1 msec,
3 pulses, repeating once per
2 seconds.
130 VAC for 200 msec, one-
time for shorted output
circuit
Heat Dissipation
33 Watts, 111 BTUs/hour