(T3464) AC Guarded Digital Output Module


P D - 6 0 2 1 M a r - 0 6

21

Load Current (maximum)

1 amp maximum per output
0

°

to 40

°

C, derated linearly

to 0.5 amp at 60

°

C

16 amps maximum per
module at 0

°

C, derated

linearly to 8 amps at 60

°

C

Load Current (minimum)

Guarded mode:

Fault tolerant mode:


50 mA
150 mA

Line Current

Load current plus 16 amps
transient during crowbar
actuation

Neutral Current

16 amps maximum transient
during crowbar actuation

On State Drop

1.6 V, maximum

Surge Current

10 amps for 20 msec

Output Leakage

Guarded mode:

Fault tolerant mode:


5 mA maximum at 60 Hz
10 mA maximum at 60 Hz

Fusing

One 2 A, 250 V, fast acting
(3AG) per output, front panel
mounted

Turn-On Delay

1 AC cycle maximum

Turn-Off Delay

1.5 AC cycle maximum

Over Voltage Protection

160 VAC, continuous

Load Bump

(Turn-on)

70 V peak for 1.1 msec,
3 pulses, repeating once per
2 seconds.
130 VAC for 200 msec, one-
time for shorted output
circuit

Heat Dissipation

33 Watts, 111 BTUs/hour