Rack 1: di, Rack 2: state, Table 5 oem parameters – Rockwell Automation T8423 Trusted TMR 35 - 120 Vdc Digital Input Module User Manual

Page 20: Table 6 rack 1: di descriptions, Table 7 rack 2: state descriptions, Trusted, Module t8423

Advertising
background image

Trusted

TM

Module T8423

Issue 15 Apr 10

PD-T8423

20

OEM Parameter

Description

Notes

TICS_CHASSIS

The number of the Trusted

TM

Chassis where the primary
I/O module is installed

The Trusted

TM

Controller Chassis is 1, and

Trusted

TM

Expander Chassis are 2 to 15

TICS_SLOT

The slot number in the
chassis where the primary
I/O module is installed

The I/O module slots in the Trusted

TM

Controller chassis are numbered from 1 to 8.
The I/O Module slots in the Trusted

TM

Expander Chassis are numbered from 1 to 12

Table 5 OEM Parameters

3.2.1. Rack 1: DI

This board provides the logical input state for each of the field inputs.

Channel

Description

1

Field input channel 1 logical state

2

Field input channel 2 logical state

40

Field input channel 40 logical state

Table 6 Rack 1: DI descriptions

The input state is reported as true (logic ‘1’) for a closed contact input, and false (logic ‘0’) for an open
contact input. The logic state is the majority voted value.

3.2.2. Rack 2: STATE

This board provides the majority voted numerical input state. This input channel state indicates the
threshold band within which the input voltage lies.

Channel

Description

1

Field input channel 1 state

2

Field input channel 2 state

40

Field input channel 40 state

Table 7 Rack 2: STATE descriptions