Table 18 default i/o status indicators, Trusted, Module t8423 – Rockwell Automation T8423 Trusted TMR 35 - 120 Vdc Digital Input Module User Manual
Page 28

Trusted
TM
Module T8423
Issue 15 Apr 10
PD-T8423
28
The configurable voltage thresholds and LED modes allow users to customise the input measurement
and status indications to suit individual application requirements. Without customisation, the default
indicator modes are suitable for digital inputs without line monitoring as described below:
Indicator State
Description
Off
Open field switch (contact) or open circuit or indeterminate
between open and closed (states 1,2,3).
Green
Closed field contact (contact) or short circuit (states 4,5).
Green – flashing
Over range (state 6).
Red – flashing
Under range or Channel Fault (states 0 or 8 to 15).
Table 18 Default I/O status Indicators
Note: The LEDs indicating channel status may be configured to suit user requirements by
implementing the procedure for configuring the SYSTEM.INI file detailed in PD-8082B.