Rack 3: ai, Table 8 rack 2: state output bit descriptions, Table 9 rack 3: channel field voltage – Rockwell Automation T8423 Trusted TMR 35 - 120 Vdc Digital Input Module User Manual

Page 21: Trusted, Module t8423

Advertising
background image

Trusted

TM

Module T8423

Issue 15 Apr 10

PD-T8423

21

Value

Description

7

Unknown

6

Over-range

5

Short circuit

4

Closed contact

3

Indeterminate

2

Open contact

1

Open circuit

0

Under-range

Table 8 Rack 2: STATE Output bit descriptions

The input channel has a value 7 (Unknown) when:

1. The input channel cannot be correctly measured by two or more slices of the TMR input

module.

2. The TMR Processor detects a 2-oo-3 channel discrepancy between the three slices of the

TMR input module.

3. The module is simulated (not installed or the TMR Processor cannot communicate with 2-oo-

3 slices of the module).

3.2.3. Rack 3: AI

The AI board returns the field loop voltage at the input.

Channel

Description

1

Field input channel 1 voltage

2

Field input channel 2 voltage

40

Field input channel 40 voltage

Table 9 Rack 3: Channel Field Voltage

The voltage is the median value taken from the triplicated module. The voltage level is reported as an
integer, with the units being

1

/

128

V. This may be used directly, scaled arithmetically or scaled using the

IEC1131 TOOLSET conversion tables.

When used directly the value may be considered as a signed, fixed-point binary value, i.e.:

Bit
15

14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Sign

Integer

Fractional

Table 10 Rack 3: Channel Field Voltage bit definitions

To scale the value arithmetically, simply divide the input value by 128 to return the voltage as either a
REAL or INTEGER as required.