4.2. Module Status LEDs

There are six module status LEDs on the module front panel; three Healthy, one Active, one Standby,
and one Educated. The Healthy indicators are controlled directly by each module slice. The Active,
Standby, and Educated indicators are controlled by the FPU. The FPU receives data from each of the
module slices. The FPU performs a 2-oo-3 vote on each data bit from the slices and sets the
indicators accordingly.

The module status LED states and their meanings are described as follows:

LED

State

Description

Healthy

Off

No power applied to the module.

Amber

Slice is in the start-up state (momentary after installation or
power-up).

Green

Slice is healthy.

Red – flashing

Fault present on the associated slice but the slice is still
operational, or one 24V feed to the chassis has failed.

Red (momentary)

On installation – power applied to the associated slice.

Red

The associated slice is in the fatal state. A critical fault has
been detected and the slice disabled..

Active

Off

Module is not in the Active state.

Green

Module is in the Active (or Maintain) state.

Red – flashing

Module is in the shutdown state if the Standby LED is off.

Red – flashing

Module is in the fatal state if the Standby LED is also flashing.

Standby

Off

Module is not in the Standby state.

Green

Module is in the Standby state.

Red – flashing

Module is in the fatal state. The Active LED will also be
flashing red.

Educated

Off

Module is not educated.

Green

Module is educated.

Green – flashing

Module is recognised by the Processor but education is not
complete.

Amber - Flashing

Active/standby changeover in progress

Table 17 Module Status Indicators

4.3. I/O Status LEDs

There are 40 input channel status LEDs on the module front panel, one for each field input. These
indicators are controlled by the FPU. The FPU receives data from each of the module slices. The
FPU performs a 2-oo-3 vote on each data bit from the slices and sets the indicators accordingly.

The input status LED mode is dependent upon the voltage level of the field I/O signal. Each field input
voltage is measured and compared to six threshold levels (four configurable and two fixed) which
produce seven threshold bands. Each threshold band can be defined to have a particular indicator
mode: off, green, red, flashing green, or flashing red.