Trusted

TM

Module T8423

Issue 15 Apr 10

PD-T8423

32

6. Specifications

System Supply Voltage Range

20 to 32 Vdc

Voltage Range (Field Supply)

35 to 140 Vdc

Number of Inputs

40 Channels

Input Voltage

Measurement Range

±120V dc

Maximum Withstanding

±160V dc

Input voltage monitor absolute accuracy

0.5V dc Full Scale

Sample Update Time

0.5ms

Turn-on/off Voltage

Configurable

Circuit Type

Fault tolerant, fully triplicated with optional
line monitoring

Fusing

None, external if required

Sequence of Events

Event Resolution

Time-stamp Accuracy


1ms
±0.5 ms

Field Common Isolation

Sustained Working

Maximum Withstanding


±250V dc
±2.5kV dc

Channel to Channel Crosstalk

–40 to –60 dB

Power Consumption

15 – 20W

External Power

Expected current consumption @ 120V dc

2mA

Self-Test Interval

2 minutes

Operating Temperature

-5

°C to 60°C (23°F to 140°F)

Non-operating Temperature

-25

°C to 70°C (-13°F to 158°F)

Temperature change

0.5ºC/min

Operating Humidity

5 – 95% RH non-condensing

Environmental Specifications

Refer to Document 552517

Dimensions

Height

Width

Depth


266mm (10.5ins)
31mm (1.2ins)
303mm (12ins)

Weight

1.149kg (2.5lbs)

Real Time Clock Resolution

100

µSec

Advertising