DC Guarded Digital Output Modules (T3461A, 62A, 68A)


1 8

Industrial Control Services

Specifications

Safetybus Power

0.85 load units

Number of Outputs

Eight circuits divided into
two groups of four circuits
each

T3461A

T3462A

T3468A

Voltage Range

18 to 30 VDC

38 to 58 VDC

95 to 150 VDC

Load Current

(0 to 40

°

C)

derating

(at 60

°

C)

1 amp

0.5 amp

0.5 amp

0.25 amp

0.5 amp

0.25 amp
(130 VDC)

0.1 amp
(150 VDC)

Minimum Load

0 mA

0 mA

0 mA

On State Drop

2.5 V,
maximum

2.5 V,
maximum

2.5 V,
maximum

Surge Current

3 amps for
20 msec

3 amps for
20 msec

3 amps for
20 msec

Output Leakage

1 mA,
maximum

1 mA,
maximum

1 mA,
maximum

Fusing

(front mounted)

One 2 amp,
250 V, fast
acting (3AB),
rectifier type,
per output

One 2 amp,
250 V, fast
acting (3AB),
rectifier type,
per output

One 2 amp, 250
V, fast acting
(3AB), rectifier
type, per
output

Turn-On Delay

1 msec

1 msec

1 msec

Turn-Off Delay

1 msec

1 msec

1 msec

Output Test
Duration

1 msec,
maximum

1 msec,
maximum

1 msec,
maximum

Heat Dissipation

25 Watts,
87 BTUs/hour

18 Watts,
61 BTUs/hour

25 Watts,
85 BTUs/hour

Over Voltage
Protection

70 VDC,
continuous

110 VDC,
continuous

190 VDC,
continuous