DC Guarded Digital Output Modules (T3461A, 62A, 68A)
 
1 8  
Industrial Control Services
Specifications
Safetybus Power
0.85 load units
Number of Outputs
Eight circuits divided into 
two groups of four circuits 
each 
T3461A
T3462A
T3468A
Voltage Range
18 to 30 VDC
38 to 58 VDC
95 to 150 VDC
Load Current
(0 to 40
°
C)
derating
(at 60
°
C)
1 amp
0.5 amp
0.5 amp
0.25 amp
0.5 amp
0.25 amp 
(130 VDC) 
0.1 amp 
(150 VDC) 
Minimum Load
0 mA
0 mA
0 mA
On State Drop
2.5 V, 
maximum 
2.5 V, 
maximum 
2.5 V, 
maximum 
Surge Current
3 amps for 
20 msec 
3 amps for 
20 msec 
3 amps for 
20 msec 
Output Leakage
1 mA, 
maximum 
1 mA, 
maximum 
1 mA, 
maximum 
Fusing
(front mounted)
One 2 amp, 
250 V, fast 
acting (3AB), 
rectifier type, 
per output 
One 2 amp, 
250 V, fast 
acting (3AB), 
rectifier type, 
per output 
One 2 amp, 250 
V, fast acting 
(3AB), rectifier 
type, per 
output 
Turn-On Delay
1 msec
1 msec
1 msec
Turn-Off Delay
1 msec
1 msec
1 msec
Output Test 
Duration 
1 msec, 
maximum 
1 msec, 
maximum 
1 msec, 
maximum 
Heat Dissipation
25 Watts, 
87 BTUs/hour 
18 Watts, 
61 BTUs/hour 
25 Watts, 
85 BTUs/hour 
Over Voltage 
Protection 
70 VDC, 
continuous 
110 VDC, 
continuous 
190 VDC, 
continuous