Application, Fail-safe configuration, Fault tolerant configuration – Rockwell Automation T3468A ICS Regent DC Guarded Digital Output Modules User Manual
Page 7
 
(T3461A, 62A, 68A) DC Guarded Digital Output Modules
 
P D - 6 0 1 9 M a r - 0 6  
7
Blown Fuse Indicators
The red BLOWN FUSE indicators switch on when the 
adjacent front panel fuse opens. If all four fuses in a group 
have opened, all of the BLOWN FUSE indicators will switch 
off and the condition will be annunciated by the module’s 
FAULT indicator, which will be on. 
Application
Guarded digital output modules provide a suitable interface to 
safety-critical output devices. These safety-critical devices 
typically include solenoids, actuators, or other process 
interlock outputs. Guarded output modules can be used for 
fail-safe or fault tolerant operation. 
Fail-Safe Configuration
As shown in Figure 3, fail-safe configuration uses a single 
Guarded module. In this configuration, the worst case failure 
will cause the output to fail to the off state. 
In a fail-safe configuration, removing the module disables all 
outputs. 
Figure 3. Fail-Safe Configuration.
Fault Tolerant Configuration
For fault tolerant operation, two Guarded modules are 
connected in parallel as shown in Figure 4. In this 
configuration, operation continues even if one module fails.