DC Guarded Digital Output Modules (T3461A, 62A, 68A)
 
2  
Industrial Control Services
Module Operation
A block diagram of a typical monitored Guarded output 
module is shown in Figure 1. 
The processor modules send triplicated write data commands 
over the I/O Safetybus to the Guarded output module. 
Onboard the Guarded output modules the triplicated data are 
routed to two independent voter and I/O Safetybus logic 
sections. Each section independently votes the triplicated 
data and operates one of the two field effect transistor (FET) 
output control switches. The two FETs are connected in series 
with the load. 
Figure 1. Block Diagram of a DC Guarded Output Module.
When both circuits are on, current will flow through the 
output and energize a field load. If either switch is off, current 
will not flow through the output and the load will be de-