Field wiring – Rockwell Automation T3468A ICS Regent DC Guarded Digital Output Modules User Manual

Page 9

Advertising
background image

(T3461A, 62A, 68A) DC Guarded Digital Output Modules


P D - 6 0 1 9 M a r - 0 6

9

Figure 5. Fault Tolerant Configuration with Redundant

Actuators.

Field Wiring

Field wiring terminal blocks on the I/O chassis are used to
connect power sources and loads to the module. The terminal
blocks are located directly above and below the slot where the
module is installed. Each terminal block consists of ten #6
wire clamp screw terminals capable of holding two 12 AWG
wires.

Each module has separate power terminals for each output
group (group 1: channels 1-4, group 2: channels 5-8). The two
groups are electrically isolated from each other (2500 volts
minimum). Figure 6 shows the proper field wiring for a single
module and Figure 7 shows the field wiring for fault tolerant
modules connected in parallel.

Two terminals are provided for connecting to each output load
device. When connected as shown in the field wiring
diagrams, each side of the output load is connected to the

Advertising