Rockwell Automation T3468A ICS Regent DC Guarded Digital Output Modules User Manual

Page 19

Advertising
background image

(T3461A, 62A, 68A) DC Guarded Digital Output Modules


P D - 6 0 1 9 M a r - 0 6

19

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-4 to output group
5-8)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

ANSI/IEEE C37.90 - Surge

Withstand Capability


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
2.5 kV damped 1 MHz sine
wave,

4 kV bi-directional impulse,
10 nsec rise time, fast
transient

Safety

Certified to DIN V VDE
0801 for Risk Class 5. Also
designed to meet UL 508 and
CSA 22.2, No. 142-M1981

Dimensions

Height:

Width:

Depth:


12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)

Weight

3.5 lbs (1.6 kg)