Rockwell Automation 20D PowerFlex 700H/S Frame 10 Replacement Power Structure User Manual

Page 10

Advertising
background image

10

PowerFlex® 700S and 700H Frame 10 Replacement Power Structures

Step 5: Connecting the
Power Structure to
Components in the Drive

You must connect the new power structure to the components in the drive. If
the drive has DC input, you must also connect the pre-charge circuit.

Connections to the 700S Control

When installing a power structure in a PowerFlex 700S drive, you must
make the following connections between the ASIC board and the Fiber
Optic Interface, Power Supply Voltage Feedback, Common Mode Filter and
Rectifier boards.

Connect this component: termination point in
the Power Structure to …

…this component : termination point on the
Control Frame

ASIC Board: H1 (fiber optic connector)

Fiber Optic Interface Board: J8 (fiber optic
connector)

ASIC Board: H2 (fiber optic connector)

Fiber Optic Interface Board: J9 (fiber optic
connector)

ASIC Board: H3 (fiber optic connector)

Fiber Optic Interface Board: J10 (fiber optic
connector)

ASIC Board: H4 (fiber optic connector)

Fiber Optic Interface Board: J11 (fiber optic
connector)

ASIC Board: H5 (fiber optic connector)

Fiber Optic Interface Board: J12 (fiber optic
connector)

ASIC Board: H6 (fiber optic connector)

Fiber Optic Interface Board: J14 (fiber optic
connector)

ASIC Board: H7 (fiber optic connector)

Fiber Optic Interface Board: J13 (fiber optic
connector)

ASIC Board: X10

Insulate and do not connect

ASIC Board: X2

Rectifier Board: X13

Power Supply Voltage Feedback Board: J8

Common Mode Filter Board: J5

Power Supply Voltage Feedback Board: J4
(fiber optic connector)

Fiber Optic Interface Board: J6

Power Supply Voltage Feedback Board: J6
(fiber optic connector)

Fiber Optic Interface Board: J7

Advertising
This manual is related to the following products: