Step 1: configuring the new power structure – Rockwell Automation 20D PowerFlex 700H/S Frame 10 Replacement Power Structure User Manual

Page 3

Advertising
background image

PowerFlex® 700S and 700H Frame 10 Replacement Power Structures

3

Step 1: Configuring the
New Power Structure

Before configuring the new power structure you must remove the protective
covers. Refer to the Installation Instructions - PowerFlex 700S and 700H
High Power Drives,
publication PFLEX-IN006

for instructions on

removing these covers.

Configuring a DC Input Drive

Power structures are shipped from the factory pre-configured for DC input
operation.

Connecting an AC Input Drive

Power structures are shipped from the factory pre-configured for DC input
operation. When installing a replacement power structure on a drive with
AC input, you must remove the X2 plug from it’s protective sleeve and plug
the cable into the ASIC and Rectifier board.

Figure 1 ASIC Board Connections

Task

Description
Remove the screw that secures the X6 connector wire to the ASIC cover and remove the
wire.
Remove the remaining screws that secure the cover to the ASIC assembly and remove the
cover.
Disconnect the ASIC fan from the assembly by unplugging the cable from X1 on the ASIC
board (see

Figure 1

below for location).

Remove the cover from the connector on the loose cable (bundled with the flat gate driver
board cables) and connect the cable to the X2 connector on the ASIC board (see

Figure 1

below for location).
Connect the other end of the cable connected to X2 on the ASIC board to the X13
connector for the Rectifier board on the upper right side of the power structure.
Connect the fan cable to the X1 connector on the ASIC board.

Install the cover on the ASIC board assembly.

A

B

C

D

E

F

G

H11

H12

H13

H8

H9

H10

X6

X9

X15

X3

X4

X5

X2

X1

H4

H5

H6

H1

H2

H3

H7

Connect cable to
X2 connector

X1 connector

Advertising
This manual is related to the following products: