8

PowerFlex® 700S and 700H Frame 10 Replacement Power Structures

Disconnect the Small Capacitors from the Input Terminals

Follow the lettered steps below to disconnect the small capacitors from the
input terminals:

Important: Do not re-install the capacitor leads.

Task

Description
Remove the screws and lock washers that secure each of the three capacitor supply wires
to the input power terminals.
Insulate the capacitor leads and leave disconnected.

Install and tighten the screws and lock washers only.

A

B

C

L1

L2

L3

Capacitor

Insulator

Capacitor lead -
leave disconnected

Input power terminal

A

B

C

Front View of Input
Power Terminals

Side View of Input
Power Terminals