Disconnect the Small Capacitors from the Input Terminals
Follow the lettered steps below to disconnect the small capacitors from the 
input terminals: 
Important: Do not re-install the capacitor leads.
Task
Description
Remove the screws and lock washers that secure each of the three capacitor supply wires 
to the input power terminals.
Insulate the capacitor leads and leave disconnected.
Install and tighten the screws and lock washers only.
A
B
C
L1
L2
L3
Capacitor
Insulator
Capacitor lead - 
leave disconnected
Input power terminal
A
B
C
Front View of Input 
Power Terminals
Side View of Input 
Power Terminals