2.2. Field Power Connection

May be connected at the T8871 Field Termination Adapter. However Field Power may be connected
any where along the cable by pulling the Field Power Cables (Grey & White) out of the outer sheath
and connecting onto suitable junction boxes.

2.2.1. Cable Impedance

Custom length multi-core FTA cables are 0.5mm

2

with a resistance of 40M/km. eg a 50m cable will

have 4M loop impedance at 0.5A, this equates to a 2Vdc volt drop.

2.3. Termination

Unused channels should be commanded OFF and may be fitted with a 33k 2W resistor to prevent no-
load detection.

2.4. Module Pinout Connections

Field Connections are made to the Modules DIN41612 type D Field Connector:

Table 2 Field Connector Pin-Out

Pin No.

Row a

Row c

2

(SMART_SLOT_A)

(SMART_SLOT_B)

4

(SMART_SLOT_C)

spare

6

V_RET_CH9_16

V_RET_CH1_8

8

V_FIELD_CH9_16

V_FIELD_CH1_8

10

V_FIELD_CH9_16

V_FIELD_CH1_8

12

V_FIELD_CH9_16

V_FIELD_CH1_8

14

V_FIELD_CH9_16

V_FIELD_CH1_8

16

V_FIELD_CH9_16

V_FIELD_CH1_8

18

LOAD_CH9

LOAD_CH1

20

LOAD_CH10

LOAD_CH2

22

LOAD_CH11

LOAD_CH3

24

LOAD_CH12

LOAD_CH4

26

LOAD_CH13

LOAD_CH5

28

LOAD_CH14

LOAD_CH6

30

LOAD_CH15

LOAD_CH7

32

LOAD_CH16

LOAD_CH8