120vac digital output module specification, Trusted, Module t8472 – Rockwell Automation T8472 Trusted TMR 120V ac Isolated Output Module User Manual

Page 27

Advertising
background image

Trusted

TM

Module T8472

Issue 13 Sep 11

PD-T8472

27

6. 120VAC Digital Output Module Specification

System Supply Voltage Range

20 to 32Vdc

Circuit Type

Fault tolerant, fully triplicated with quad output
switch circuits.

Number of Outputs

16 Channels

Independent Power Groups

2 each of 8 outputs

Operational Output/Field Voltage Range

90 to 150VAC, 47Hz < freq < 63Hz

Output Voltage

Measurement Range

150VAC(RMS)

Maximum Withstanding

175VAC(RMS)

Output Current Rating

Continuous ( Imax per channel )

Continuous ( Imax per power group )

Channel surge


0.5A
4A
8A peak (1 AC cycle)

Minimum On State Load Current

10mA

Power Consumption

System Supply (24V)


17W

Field Common Isolation

Sustained Working

Maximum Withstanding


±250Vdc
±2.5kVdc

Output Off State Leakage

2mA max at 150VAC

Output On State Switch Voltage Drop

1VAC (RMS) max at 0.5A loading

Output Short Circuit Protection

Electronic

Output Turn-on/off Delay

1.5 AC cycle max. (zero crossing)

Channel Monitor Update

Every 16 AC cycles

Sequence of Events

Event Resolution


1ms

Channel Test Interval

1 minute

Intrinsic Safety

External barrier

Operating Temperature

-5

°C to 60°C (23°F to 140°F)

Non-operating Temperature

-25

°C to 70°C (-13°F to 158°F)

Temperature change

0.5ºC/min

Operating Humidity

5 – 95% RH non-condensing

Environmental Specifications

Refer to document 552517

Dimensions

Height

Width

Depth


266mm (10.5ins)
31mm (1.2ins)
303mm (12ins)

Weight

1.342Kg (3lb)

Advertising