Trusted, Module t8472, Rack 1: do – Rockwell Automation T8472 Trusted TMR 120V ac Isolated Output Module User Manual

Page 15: Rack 2: state

Advertising
background image

Trusted

TM

Module T8472

Issue 13 Sep 11

PD-T8472

15

OEM Parameter Description

Notes

TICS_CHASSIS The number of the Chassis

where the Primary I/O
module is installed

The Controller Chassis is 1, and Expander
Chassis are 2 to 15

TICS_SLOT

The slot number in the
chassis where the Primary
I/O module is installed

The I/O module slots in the Controller chassis are
numbered from 1 to 8. The I/O Module slots in the
Expander Chassis are numbered from 1 to 12

Table 4 OEM Parameters

3.2.1. Rack 1: DO

This board provides the connection to the logical output control signal for each of the field outputs.

Channel

Description

1

Field output channel 1 logical state

2

Field output channel 2 logical state

16

Field output channel 16 logical state

Table 5 Rack 1: DO descriptions

The user application should set the output control signal to true (logic ‘1’) to turn ON or energise an
output, and false (logic ‘0’) to turn OFF or de-energise an output.

3.2.2. Rack 2: STATE

This board provides the majority voted numerical output state. This indicates the operational status of
the output channel and associated field connection.

Channel

Description

1

Field output channel 1 state

2

Field output channel 2 state

16

Field output channel 16 state

Table 6 Rack 2: STATE descriptions

Advertising