Trusted, Module t8472, Rack 3: ai - channel field voltage – Rockwell Automation T8472 Trusted TMR 120V ac Isolated Output Module User Manual

Page 16

Advertising
background image

Trusted

TM

Module T8472

Issue 13 Sep 11

PD-T8472

16

Value

Description

7

Channel fault

6

Field fault (e.g. field leakage to 0V or 24V)

5

Short circuit in field wiring or load

4

Output energised (ON)

3

Open circuit in field wiring or load

2

Output de-energised (OFF)

1

No field supply voltage

0

Unused

Table 7 Rack 2: STATE Output descriptions

3.2.3. Rack 3: AI - Channel Field Voltage

The AI board returns the field loop voltage at the output.

Channel

Description

1

Field output channel 1 voltage

2

Field output channel 2 voltage

16

Field output channel 16 voltage

Table 8 Rack 3: AI descriptions

The voltage is the median value taken from the triplicated module. The voltage level is reported as an
integer, with the units being

1

/

125

V. This may be used directly, scaled arithmetically or scaled using the

IEC1131 toolset conversion tables.

To scale the value arithmetically simply divide the returned ‘integer’ by 125 to return the voltage as
either a REAL or INTEGER as required.