Thermocouple Input Assembly (T3431)


1 2

Industrial Control Services

Thermocouple Multiplexer Configuration

The thermocouple input multiplexer provides jumpers to
configure the thermocouple types, noise filtering, temperature
units, and temperature resolution. All thermocouple
configuration jumpers are located on the component side of
the Mux as shown in Figure 7. To access these jumpers the
Mux must be removed from the termination panel.

Figure 7. Location of Configuration Jumpers on Mux.

Thermocouple Type Configuration

Each group of eight inputs, 1-8, 9-16, and 17-24, is
individually configured for thermocouple type J, K, S, or T
using three jumpers for each group of inputs. The three
jumpers are labeled Bit 4, Bit 2 and Bit 1. The jumper
settings for each thermocouple type are shown in Table 1.

Table 1. Thermocouple Type Jumper Settings.

Thermocouple Type

Bit 4

Bit 2

Bit 1

J

Low

Low

Low

K

Low

Low

High

S

High

Low

Low

T

High

Low

High

To assign the thermocouple type, find the associated jumper
block for the group T/C 1-8, T/C 9-16, or T/C 17-24 and place
each jumper next to the appropriate high or low designation.