Safety considerations, Specifications – Rockwell Automation T3431-CA ICS Regent Thermo Couple Input Assembly User Manual

Page 24

Advertising
background image

Thermocouple Input Assembly (T3431)


2 4

Industrial Control Services

Safety Considerations

The thermocouple input modules are TÜV certified as non-
interfering and can be used for non-safety critical inputs in
Risk Class 5 safety applications.

For additional safety considerations, please refer to the Safety
Considerations section of the Regent User’s Guide.

Specifications

Safetybus Power

1.8 load units (input module)

Number of Inputs

24 differential

Thermocouple Input Types

Type J:
Type K:
Type S:
Type T:


Iron/constantan
Chromel/alumel
Pt/Pt-10% Rh
Copper/constantan

Thermocouple Units

Degrees Centigrade or
degrees Fahrenheit

Thermocouple Resolution

Tenths or units

Thermocouple Ranges

Type J:


Type K:


Type S:


Type T:


0

°

to +750

°

C

(+32

°

to +1382

°

F)

-200

°

to +1250

°

C

(-328

°

to +2282

°

F)*

0

°

to +1450

°

C

(+32

°

to +2642

°

F)*

-200

°

to +350

°

C

(-328

°

to +662

°

F)

*

If 0.1

°

F resolution is selected,

the maximum usable temperature
is +1638.3

°

F

Thermocouple Burnout

Downscale driven

Differential Input Resistance

2M ohms (typical)

Advertising