Thermocouple terminations – Rockwell Automation T3431-CA ICS Regent Thermo Couple Input Assembly User Manual

Page 18

Advertising
background image

Thermocouple Input Assembly (T3431)


1 8

Industrial Control Services

Thermocouple Terminations

Thermocouple wires are connected to the screw terminals
located at the bottom of the termination panel as shown in
Figure 10. When terminating thermocouple wiring, follow the
recommendations listed below.

1. Greater accuracy is maintained with a heavier gauge

thermocouple extension wire.

2. All thermocouples within a group of eight must be the

same thermocouple type.

3. Terminate unused thermocouple inputs with the same

signal as preceding inputs, or short the two input
terminals together.

4. Install the termination cover after completing the wiring

connections.

Figure 10. Wiring Thermocouples to Term Panel.