Thermocouple Input Assembly (T3431)


2 6

Industrial Control Services

Thermocouple Accuracy

Maximum error (0

°

to 60

°

C).

Add ±0.5 LSB resolution error to
the following:

Type J, Full range:

Type K

< -100

°

C:

> -100

°

C:

Type S

< 540

°

C:

> 540

°

C:

Type T

< 0

°

C:

> 0

°

C:





±1.6

°

C (3.0

°

F)


±4.2

°

C (7.6

°

F)

±2.4

°

C (4.3

°

F)


±13

°

C (24

°

F)

±7

°

C (12.5

°

F)


±4.8

°

C (8.7

°

F)

±2.1

°

C (3.8

°

F)

Wire Resistance Effects

Type J, Full range:

Type K

< -100

°

C:

> -100

°

C:

Type S

< 540

°

C:

> 540

°

C:

Type T

< 0

°

C:

> 0

°

C:


-0.0020

°

C/ohm (.0036

°

F)


-0.0066

°

C/ohm (0.0120

°

F)

-0.0033

°

C/ohm (0.0060

°

F)


-0.0200

°

C/ohm (0.0360

°

F)

-0.0100

°

C/ohm (0.0180

°

F)


-0.0066

°

C/ohm (0.0120

°

F)

-0.0025

°

C/ohm (0.0045

°

F)

Adjacent Channel Effects

Channel n = top of range
channel; n-1 = bottom of range

Type J:

Type K:

Type S:

Type T:





-1.0

°

C (1.7

°

F)

-1.5

°

C (2.7

°

F)

-4.0

°

C (7.2

°

F)

-0.8

°

C (1.5

°

F)

Channel n = bottom of range; n-1
= open circuit

Type J:

Type K:

Type S:

Type T:



-3.0

°

C (5.4

°

F)

-4.0

°

C (7.2

°

F)

-30

°

C (54

°

F)

-4.5

°

C (8.1

°

F)

Advertising