Installation
2-19
Step 4.5 Fasten the right side of the AutoMax Network option board to the keypad
bracket. Use the two metal M3 screws and lock washers for grounding.
Important: You must use the lock washers to properly ground the option board.
Improper grounding of the option board can result in erratic operation of
the drive.
Step 4.6 Fasten the left side of the AutoMax Network option board to the keypad
bracket using the two plastic rivets.
Step 5.
Reinstall the Keypad Bracket in the Drive
Step 5.1 Align the Regulator board ribbon cable connector with the connector to the
Base board. Carefully press the ribbon cable connector in until the retaining
clips lock into place.
Step 5.2 Place the keypad bracket back into position.
Figure 2.10 – Regulator Board’s Connections to Option Board, Keypad, and Base Board
Regulator Board
Top View
Ribbon Cable
Connecting
Regulator Board and
Base Board
Network
To Base Board
Front
Ribbon Cable
Connecting
Regulator Board and
Option Board
Metal Screw
Ribbon Cable
Connector to
Connect Base
Board
Ribbon Cable
Connector to
Connect Keypad
Plastic Rivet
Terminal Strip
Ribbon Cable
Connector to
Connect Option
Board
Back Side of
Insulator
Rear View of Regulator Board
Regulator Board