3-2

LiquiFlo 1.5 AC Power Modules, Hardware Reference Version 1.2

3.1.2 Determining Total Area Required Based on Drive Dimensions

Drive dimensions and weights are listed in table 3.2. Overall drive dimensions are
illustrated in figures 3.1, 3.2, and 3.3 as an aid in calculating the total area required by
the LiquiFlo drives.

Table 3.1 – Environmental Conditions

Condition

Specification

Operating Temperature (inside a NEMA cabinet)

0

qCto 55qC

1

 32qto131qF

1

With typical heat rise inside a cabinet, 40

qC ambient outside usually results in 55qC inside.

Storage Temperature (Ambient)

-40

qCto65qC 40qto149qF

Humidity

5% to 95% (non-condensing)

Table 3.2 – Drive Dimensions and Weights

LiquiFlo

Drive M/N

Frame

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

Dim. G

Weight

LF150414R4

LF150414W4

B

475 mm

18.69”

800 mm

31.52”

357 mm

14.06”

397 mm

15.63”

711mm

28.00”

39 mm

1.53”

20 mm

0.79”

125 kg

275 lb

LF150500R4

LF150500W4

C

583 mm

22.96”

971 mm

38.23”

347 mm

13.66”

464 mm

18.25”

787 mm

31.00”

28 mm

1.09”

25 mm

1.00”

168 kg

370 lb

LF150643R4

LF150643W4

C

583 mm

22.96”

971 mm

38.23”

347 mm

13.66”

464 mm

18.25”

787 mm

31.00”

28 mm

1.09”

25 mm

1.00”

170 kg

375 lb

LF151200R4

LF151200W4

D

1010 mm

39.75”

1245 mm

49.00”

360 mm

14.16”

838 mm

33.00”

1200 mm

47.25”

29 mm

1.12”

25 mm

1.00”

386 kg

850 lb

Advertising