Analog Output

The single analog output channel can be configured using Analog Out Config (340)
and Analog Out1 Sel (342) to select any one of 13 analog outputs. Terminals 1 and 2
output 4 to 20 mA. Terminals 17 and 18 output -10 to +10 volts. See table 7.1

Analog Out1 Sel (342) can be assigned the following values:

Table 7.1 – Analog Output Connection (Terminals 1- 2 or 17-18)

Terminal #

Signal

Related Parameters

1

I1- (Current -)

Analog Out Config (340) =1

2

I1+ (Current +)

17

V1- (Voltage -)

Analog Out Config (340) = 0

18

V1+ (Voltage +)

0 = Output Freq

7 = DC Bus Volts

1 = Command Freq

8 = PI Reference

2 = Output Amps

9 = PI Feedback

3 = Torque Amps

10 = PI Error

4 = Flux Amps

11 = PI Output

5 = Output Power

12 = %Motor OL

6 = Output Volts

13 = %Drive OL