Table A.2 – Environmental Conditions
Condition
Specification
Operating Temperature (inside an enclosure)
0
qCto 55qC
*
32qFto131qF
*
User-supplied cabinet air cooling system must provide adequate heat dissipation to maintain an internal
temperature not to exceed 55
qC. Refer to table 2.1 for drive air watts loss.
Storage Temperature (Ambient)
-40
qCto65qC40qFto149qF
Humidity
5% to 95% (non-condensing)
Motor Overload Protection
Electronic Motor
Overload Protection
Provides class 10 motor overload protection according
to NEC article 430. Does not provide speed sensitive
overload protection, thermal memory retention, and
motor over-temperature sensing according to NEC
article 430.126 (A) (2). If such protection is needed in
the end-use product, it must be provided by additional
means.