Rockwell Automation MPP Processor Moduile User Manual
Page 16
Advertising
16
MPP October 2005 – Issue 6
Triguard SC300E
Table 2-3. Configuration register switch settings for baud rate
Switch position
Baud rate
Switch position
Baud rate
S 1-5
S- 1-6
S 1-7
957 Monitor
S 2-5
S 2-6
S 2-7
CSI/O OFF
OFF
ON
ON
1200
OFF
ON
ON
1200
ON
ON
ON
19200 (Default)
ON
ON
ON
19200
NOTE
The diagram below (Figure 2-6 ) shows S1 in its default condition, i.e. elements
3, 5, 6, 7 and 8 all ON (CLOSED), and, elements 1, 2 and 4 all OFF (OPEN).
Figure 2-6 Switch S1 shown in Default condition
Table 2-4. Pinout for front panel diagnostic
Pin
Signal
Pin
Signal
1
Unused
6
DSR
2
RxD
7
RTS
3
TxD
8
CTS
4
DTR
9
Unused
5
0V
-
-