MPP October 2005 – Issue 6

21

Triguard SC300E MPP Processor Module

The locations of the links are shown in general view showing link locations.

Table 3-1. Module link settings

Fit Link

Across Pins

For Condition

Factory default

LK1

1 & 2

Data error monitoring

Yes

LK1

2 & 3

8MHz clock

No

LK2

Fit link

RTS-CTS loopback

Yes

LK3

1 & 2

5ms real time clock

No

LK3

2 & 3

10ms real time clock

Yes

LK4

1 & 2 and 3 & 4

Loopback operation

No (test use only)

LK5

1 & 2

4Mbit RAM devices

No

LK5

2 & 3

1Mbit Ram devices

Yes

LK6

1 & 2 and 3 & 4

Loopback operation

No (test use only)

LK7

Fit link

Write operations to flash memory

No

LK8

1 & 2

1Mbit or 2Mbit EPROMs

Yes

LK8

3 & 4

<1Mbit EPROMs

No

LK9

1 & 2 and 3 & 4

Loopback operation

No (test use only)

LK10

Fit link

Slow EPROM (

<

70ns)

Yes

LK11

Fit all links

Loopback operation

No (test use only)

LK12

Fit link

CPU self test

Yes

LK13

Fit link

Supervisory watchdog

No

LK14

Position 1

Logic 5V

Not applicable on
Modules at Rev 04
and above

LK14

Position 2

Battery backup enabled

No

LK14

Position 3

Battery backup disabled

Yes