2.2.4. Digital Output Boards

Figure 12 shows the display associated with an IEC1131 Toolset 16 channel digital output board
selected for outgoing data to a Trusted

TM

controller.

Figure 12 Peer to Peer Digital Output Board Display

The user must enter data as detailed below:

NETWORK_ID – The network that is carrying the data. Data will be received via all peer controllers
that share this network identity. Range 1 – 8.

TARGET_PEER_ID - The peer that is receiving the data, or the multicast ‘peer’. Range 1 – 40.

SOURCE_DATA_ID - Unique data block number to allow input boards to distinguish the data.
Range 1-64.

REFRESH_INTERVAL - The maximum number of milliseconds allowed between successive
transmissions of the output data. Note that data will be sent immediately following any change of
output state. If a value of zero is specified in this field then data will be refreshed every application
scan regardless of output state change. Range 0-10000.

Boolean variable outputs 1 to 16 – Boolean outputs.

The 128 output peer board supports 128 Boolean outputs instead of 16.