Trusted, Communication software package t8017 – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual

Page 33

Advertising
background image

Trusted

TM

Communication Software Package T8017

Issue 10 Mar 08

PD-T8017

33

Dual Peer to Peer Analogue Output (data is sent via both subnets automatically).

dxpao – DATA rack

Value

Comment

NETWORK_ID

1

Network 1

TARGET_PEER_ID

2

This output is going to PEER_IP_02.

SOURCE_DATA_ID

1

Will transmit data ID 1. This is a unique packet ID to
enable the system to distinguish between different data
packets routed between the same source and
destination.

REFRESH_TMO

2000

Maximum time peer data is sent if no change of
application values above the MIN_DELTA has
occurred.

MIN_DELTA

20

The value change that is required before the data will
be transmitted. If the value change is less than this, the
value will be transmitted based on the
REFRESH_TMO setting.

Variable 1 - 16

Analogue

Output

Analogue output points.

Table 10 Example 2 - PEER_IP_02 Analogue Output (data sent automatically)

Dual Peer to Peer Analogue Output (data is sent via both subnets automatically).

dxpao – DATA rack

Value

Comment

NETWORK_ID

1

Network 1

TARGET_PEER_ID

3

This output is going to PEER_IP_03.

DATA_ID

2

Will transmit data ID 1. This is a unique packet ID to
enable the system to distinguish between different data
packets routed between the same source and
destination.

REFRESH_TMO

2000

Maximum time peer data is sent if no change of
application values above the MIN_DELTA has
occurred.

MIN_DELTA

20

The value change that is required before the data will
be transmitted. If the value change is less than this, the
value will be transmitted based on the REFRESH_TMO
setting.

Variable 1 - 16

Analogue

Output

Analogue output points.

Table 11 Example 2 - PEER_IP_03 Analogue Output (data sent automatically)

Advertising