Trusted, Communication software package t8017 – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual
Page 32

Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08
PD-T8017
32
Dual Peer to Peer Digital Input (data is received via both subnets automatically).
dxpdi – DATA rack
Value
Comment
NETWORK
1
Network 1
SOURCE_PEER
3
This data must originate from the controller with IP
specified in PEER_IP_03.
SOURCE_DATA_ID
1
Will receive data ID 1. This is a unique packet ID to
enable the system to distinguish between different
data packets routed between the same source and
destination.
REFRESH_TMO
5000
Maximum time allowed before data is declared
invalid.
FS_VALUE
FALSE
Fail safe state.
DATA rack
Variable 1 - 16
Boolean
Digital Input points. Directly mapped to the points on
the output board in controller 3.
STATUS rack
Variable 1
Boolean Input TRUE = data is valid. Will go to FALSE if the
REFRESH_TMO times out.
Variable 2 - 9
Boolean Input Data has been refreshed within the REFRESH_TMO
by subnets 1-8 respectively.
CONTROL rack
Variable 1
Boolean
Output
FALSE = Force data to FALSE when invalid.
TRUE = Allow previous value to persist when data is
invalid.
Table 9 Example 2 - Digital Input (data received automatically from subnets)