2.4. Peer to Peer Configuration Example 2

Figure 13 shows an example configuration for a system using 4 controllers connected together
using one peer to peer network with dual physical network paths, but this time with multicast
data.

In this example, Controller 4 will be the master of network 1 subnet 1. Controller 1 will be the
master of network 1 subnet 2.

• 16 digital points will be sent from controller 3 to controllers 1, 2 & 4 via a multicast

configuration.

• 16 analogue points will be sent from controller 1 to controller 2.
• A separate set of 16 analogue values will be sent from controller 1 to controller 3.
• 16 digital values will be sent from controller 2 to controller 4.

2.4.1.

Controller 1 settings

Dual Peer to Peer Net Control, network 1 subnet 1.

dxpnc40 –
CONTROL rack

Value

Comment

CHASSIS

1

Communication module located in chassis 1.

SLOT

7

Communication module is located in slot 7.

NETWORK_ID

1

Network 1

SUBNET_ID

1

Subnet 1

PEER_ID

1

Identity of this controller.

RESPONSE_TMO

0

Default

REFRESH_TMO

2000

Default

TX_DATA_TMO

500

Default

Variable 1

TRUE

Enable Peer to on this subnet.

Variable 2

FALSE

This is a slave connection.

PEERS_1 rack

PEER_IP_01

10.10.1.1

Controller 1, network 1, subnet 1

PEER_IP_02

10.10.1.2

Controller 2, network 1, subnet 1

PEER_IP_03

10.10.1.3

Controller 3, network 1, subnet 1

PEER_IP_04

10.10.1.4

Controller 4, network 1, subnet 1

PEER_IP_05

239.255.1.1

Multicast address

Table 7 Example 2 - Controller 1 Settings Control, network 1 subnet 1