What you need – Rockwell Automation 1769-L30ER_L30ERM_L30ER-NSE_L33ERM_L33ER_L36ERM CompactLogix 5370 L3 Controllers Quick Start User Manual

Page 51

Advertising
background image

Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012

51

Configure the EtherNet/IP Network Chapter 3

What You Need

Table 6

lists the software components you use in this chapter.

Assign an IP Address to the Controller Over a USB Connection

At initial powerup, the CompactLogix 5370 L3 controller does not have an IP address. Use
RSLinx Classic software over a USB connection to assign an IP address. If the computer with
RSLinx Classic software is not connected to the controller via a USB connection, the following
steps will not work.

1. Verify that your computer is connected to the USB port on the front of the controller.

Table 6 - What You Need to Configure the EtherNet/IP Network

Component

Description

Studio 5000 environment

Environment that combines engineering and design elements into a common environment.

Logix Designer application

Application used to create a project the CompactLogix 5370 L3 controller uses in your application.

RSLinx Classic software

Communication server that supports multiple software applications simultaneously, establishing
communicating between devices on many different Rockwell Automation industrial networks.

IP address

A number in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254.

The IP address uniquely identifies the controller on the EtherNet/IP network.

Subnet mask

Extension of the IP address that allows a site to use a single network ID for multiple
physical networks.

If you change the subnet mask of a configured controller, you must cycle power to the controller
for the change to take effect.

IMPORTANT

There are other methods to assign an IP address to the controller, such as using the BOOTP/DHCP utility. This section is
only one example of how to assign the IP address to the controller.

For more information on the methods of assign an IP address to the CompactLogix 5370 L3 controller, see the
CompactLogix 5370 Controllers User Manual, publication

1769-UM021

.

Advertising