Trane Liqui-Flo Addendum

Table 2.1 – Power and Enclosure Ratings

2.2

Enclosure Rating

The Trane cabinet has a NEMA 1 enclosure rating:

NEMA 1: Vented. Intended for general-purpose indoor applications.

NEMA 1 enclosures are to be located in a clean and dry environment that is away
from oil, coolant, or other airborne contaminants.

2.3

Identifying Trane Cabinet Components

The 6-pulse rectifier Trane cabinets have the following main components. The
identification numbers provided correspond to the numbers used in figure 2.2.

Trane Cabinet M/N

Reliance

Liqui-Flo

Drive M/N

Frame

Size

Cabinet

Enclosure

Rating

Input

Power

(KVA)

Input

Current

(Amps)

Output

Current

at 2 kHz

(Amps)

Full Load

Power

Loss Watts

AFDB0643GA0A10

64L4060

C

NEMA 1

555

667

643

9500

1.

Cabinet

2.

Control Panel Assembly

3.

C-Frame Liqui-Flo Drive

4.

Liqui-Flo Power Module Adapter Board - Provides the interface between the drive’s
electronics and power structure

5.

Liqui-Flo Bus Control Board - Controls the drive’s power supplies and SCRs

6.

Liqui-Flo Regulator Board - Controls overall drive operation

7.

Super Remote Meter Interface (RMI) Board - Provides additional analog I/O (located
under the Regulator board)

8.

Coolant Lines - (a) Outlet, (b) Inlet

9.

Motor Connection Studs (6) P/O CTV

10.

AC Input Bus Bars (6-Pulse Rectifier)

11.

Current Transformers (3) - Used by the Trane UCP2 Control Panel to monitor output
current

12.

1200 A Circuit Breaker

13.

4 KVA Transformer - Steps down the 480 VAC input voltage to 115 VAC

14.

(3) Type RK-5 Fuses - Protect the primary of the 4 KVA transformer - (1 fuse: 2 amp)
(2 fuses: 15 amp)

15.

(2) Type K5Fuses - Protect the coolant pump’s reactor (1 fuse: 10 amp) and the Starter
module’s 115 VAC line (1 fuse: 30 amp)

16.

Terminal Block - Provides termination points for cabinet I/O wiring

17.

Potential Transformers (3) - Used by the Trane UCP2 Control Panel to measure the
480 VAC input voltage

18.

Trane Starter Module - Interfaces the Liqui-Flo drive to the Trane UCP2 Control Panel

19.

Relay 2K1 - Circulating coolant pump motor interposing relay

20.

Relay 2K2 - Oil pump interposing relay

21.

Relay 2K3 - Run/stop function interposing relay

22.

50 VA Transformer 460VAC / 115VAC/ 24 VAC - Supplies power to the Trane Starter
Module

23.

Fan - Provides cooling for the DC bus reactor

24.

Removable Plate - Provides chain hoist access

25.

Surge Suppressor