Cabinet Mounting, Wire Routing, and Liquid-Cooling Connections

3-1

C

HAPTER

3

Cabinet Mounting, Wire Routing,

and Liquid-Cooling Connections

This chapter provides cabinet dimension information that must be considered when
installing a Trane cabinet. It describes how to mount the Trane cabinet and shows
where the wire entry areas and liquid-cooling connection points are located.

3.1

Planning the Cabinet Installation

Cabinet dimensions and weights are listed in table 3.1. Overall cabinet dimensions are
illustrated in figure 3.1. Cabinet mounting holes are shown in figure 3.2.

Be sure there is adequate clearance for air ventilation around the cabinet. Allow a
minimum clearance of 1 foot per side. Allow 4 feet of clearance for the door to open.

3.2

Mounting the Cabinet

Attach the cabinet to the CenTraVac

chiller using the 8 mounting holes provided. In

order to maintain a flat mounting surface and to ensure that screw tightness is
maintained, use a washer and lock washer under the screw heads. Refer to figure 3.1
and table 3.1 for cabinet mounting dimensions. Use 3/8” (upper) and 1/2” (lower)
mounting screws and washers to attach the cabinet to the chiller. See figure 3.2 and
table 3.2 for mounting hole locations and dimensions.

Table 3.1 – Cabinet Dimensions

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

Weight

965 mm

38.0"

1524 mm

60.0"

379 mm

15.1"

1608 mm

63.3"

60 mm

2.4"

23 mm

0.91"

440 kg

970 lbs

Table 3.2 – Cabinet Mounting Hole Dimensions

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

Dim. G

1268.4mm

49.94"

85.7mm

3.38"

114.3mm

4.5"

314.3mm

12.38"

127.0mm

5.0"

254.0mm

10.0"

660.4mm

26.0"