Run mode, Self-diagnostic error mode – Banner U-GAGE T30U—Level Control User Manual

Page 4

Advertising
background image

Teach First

Limit

Output 2

Limits Only

Teach Second

Limit

Teach First

Limit

Teach First Limits

Teach Second Limits

Push Button Locked out

(or Enabled)

Output 1

Limits Only

Teach Second

Limit

Both Outputs

Together

Push Button

Lockout

(or Enable)

T

> 0.8 sec

> 0.8 sec

T

T

T

T

T

T

T

T

T

T

T

T

T

T

> 0.8 sec

T

T

T

T

0.04 sec < T < 0.8 sec

Figure 6. Timing programs for remote TEACH programming

NOTE: Hold the Remote line high > 2 seconds (before teaching the second limit) to exit Program mode without saving any changes. The
sensor will revert to the last saved program.

Run Mode

NOTE: All LED indicators momentarily go OFF when sensor changes state between Program and Run modes.

Signal LED
The Red Signal LED indicates the strength and condition of the sensor’s incoming signal.

Signal LED Status

Indicates

OFF

No signal is received, or the target is beyond the range limitations of the sensor (with some tolerance beyond the recommen-
ded minimum and maximum sensing distance)

Flashing

Relative received signal strength; the faster the LED flashes, the stronger the signal

Output LEDs
Each Yellow Output LED lights when a target is sensed within the programmed window limits.
Power ON/OFF LED
The Green Power ON/OFF LED indicates the operating status of the sensor.

Power ON/OFF LED

Indicates

OFF

Power is OFF (or in Program mode, if other LEDs are ON)

ON Solid

Sensor is operating normally (power is ON, Run mode)

Flashing

Discrete output is overloaded (Run mode)

Self-Diagnostic Error Mode

In the unlikely event of a microprocessor memory error, all of the LEDs will flash in sequence. If this occurs, the setup parameters have been lost and the sensor may be
corrupt. Contact Banner Engineering for further information.