Dimensions, Hookups – Banner U-GAGE T30U—Level Control User Manual

Page 6

Advertising
background image

with Rod Target (Typical)

0

50

50

100

100

150

150

200

200

0

200 mm

(8.0 in)

400 mm

(16.0 in)

600 mm

(24.0 in)

800 mm

(32.0 in)

1000 mm

(40.0 in)

0

2.0 in

2.0 in

4.0 in

4.0 in

6.0 in

6.0 in

8.0 in

8.0 in

25 mm Rod

10 mm Rod

DISTANCE

WIDTH

(mm)

Figure 9. 1-Meter Models

0

100

100

200

200

300

300

400

400

DISTANCE

0

400 mm

(16.0 in)

800 mm

(32.0 in)

1200 mm

(48.0 in)

1600 mm

(64.0 in)

2000 mm

(80.0 in)

0

4.0 in

4.0 in

8.0 in

8.0 in

12.0 in

12.0 in

16.0 in

16.0 in

25 mm Rod

WIDTH

(mm)

Figure 10. 2-Meter Models

Dimensions

M30 x 1.5

Thread

ø 40.0 mm

(1.57")

Cabled Models

Quick-Disconnect Models

Jam Nut

(Supplied)

45.0 mm

(1.77")

ø 15 mm

(0.59")

11.5 mm

(0.45")

51.5 mm

(2.03")

66.5 mm

(2.62")

Hookups

Shield*

12-24V dc

+

1

3

2

4

5

Remote
Teach

Output 1

Output 2

Figure 11. Cabled NPN

Shield*

12-24V dc

+

1

3

2

4

5

Remote
Teach

Output 1

Output 2

Figure 12. Cabled PNP

1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray

Cable and QD hookups are functionally identical.
It is recommended that the shield wire is connected to earth ground or dc common.