tekmar 361 Mixing Control User Manual

Page 12

Advertising
background image

Copyright © D 361 -

03/09

12 of 20

Indoor Sensor

If an indoor sensor is used, connect the two wires from the sensor
to the

Com and Indr terminals (15 and 17). The indoor sensor is

used by the 361 to measure the room air temperature.

Unoccupied Switch

If an external timer (tekmar Timer 03

2) or switch is used, connect the two wires from

the external switch to the

UnO Sw and Com terminals (11 and 12). When these two

terminals are shorted together, the control registers an unoccupied signal.

STEP FIVE

TESTING THE WIRING

Each terminal block

must be unplugged from its header on the control before power is applied for testing. To remove a terminal block,

pull it straight down from the control.

The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly
trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to
properly test the wiring and sensors.

Test The Sensors

In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with a
surface temperature probe is recommended for ease of use and ac-
curacy. Where a digital thermometer is not available, a spare sensor
can be strapped alongside the one to be tested and the readings
compared. Test the sensors according to the instructions in the Data
Brochure D 070.

Test The Power Supply

Make sure exposed wires and bare terminals are not in contact with
other wires or grounded surfaces. Turn on the power and measure
the voltage between the

Power L and Power N terminals (3 and 4)

using an AC voltmeter. The reading should be between 108 and
132 V (ac).

Test The Powered Inputs

Mixing Demand

Measure the voltage between the

Mixing Demand terminals (1 and

2). When the mixing demand device calls for heat, you should
measure between 20 and 260 V (ac) at the terminals. When the
mixing demand device is off, you should measure less than 5 V (ac).

V

V

1

2

Mixing

Demand

20 to 260 V (ac)

V

V

3

4

L

N

Power

108 to 132 V (ac)

15

16

17

Com

Indr

Out

13

14

Boil

Mix

12

Com

V

Timer Switch

11 12

UnO

Sw

Com