Adjust Menu (1 of 2)

The type of terminal units that are being used in the
heating system.
(OUTDR DSGN

OFF)

1 (High Mass Radi-
ant), 2 (Low Mass
Radiant), 3 (Fancoil),
4 (Fin-tube Convec-
tor), 5 (Radiator),
6 (Baseboard)

B2

The desired room air temperature during an
occupied (Day) period.
(OUTDR DSGN

OFF)

35 to 100

°F

(2 to 38

°C)

B2

The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN

OFF)

35 to 100

°F

(2 to 38

°C)

B2

Mixing setpoint temperature.
(OUTDR DSGN = OFF)

60 to 200

°F

(16 to 93

°C)

The design outdoor air temperature used in the
heat loss calculation for the heating system. For
setpoint operation, set the OUTDR DSGN to OFF.

-60 to 32

°F, OFF

(-51 to 0

°C, OFF)

Display

Description

Range

The design supply water temperature used in the
heat loss calculation for the heating system.
(OUTDR DSGN

OFF)

70

°F to 220°F

(21 to 104

°C)

B3

The design indoor air temperature used in the heat
loss calculation for the heating system.
(OUTDR DSGN

OFF)

35 to 100

°F

(2 to 38

°C)

B3

The maximum supply temperature for the mixing
system.
(OUTDR DSGN

OFF)

80 to 210

°F

(27 to 99

°C)

B3

The minimum supply temperature for the mixing
system.
(OUTDR DSGN

OFF)

OFF, 35 to 150

°F

(OFF, 2 to 65

°C)

The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)

OFF, 80 to 180

°F

(OFF, 27 to 82

°C)

C1

The differential that the control is to use when it is
operating the boiler.
(

Boiler Sensor DIP switch = Supply AND Boiler

sensor is present)

Ad, 2 to 42

°F

(Ad, -17 to 6

°C)

C2

B3

B2

B2

Section

Advanced

Installer

Actual

Setting

ADJUST

INDR

MIX

°

F

ADJUST

DSGN

MIX

°

F

ADJUST

MIX

°

F

MAX

ADJUST

BOIL

°

F

MIN

ADJUST

DIFF

BOIL

ADJUST

ROOM

°

F

OCC

UN

ADJUST

Terminal Unit

ADJUST

DSGN

OUTDR

°

F

ADJUST

ROOM

°F

OCC

ADJUST

MIX MIN

ADJUST

TARGET

MIX

°F