Testing the Control

The Mixing Control 361 has a built-in test routine which is used to test the
main control functions. The 361 continually monitors the sensors, and
displays an error message whenever a fault is found. See the following
pages for a list of the 361’s error messages and possible causes. When
the

Test button is pressed, the test light is turned on. The individual

outputs and relays are tested in the following test sequence.

TEST SEQUENCE

Each step in the test sequence lasts 10 seconds.

During the test routine, the test sequence may be paused by pressing the

Test button. Only if there is a mixing demand can the control

be paused in a step. If the

Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire

test routine. If the test sequence is paused, the

Test button can be pressed again to advance to the next step. This can also be used

to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the

Test button until the

appropriate device and segment in the display turn on.

Step 1

- The injection pump operates at 100% for 10 seconds. After 10 seconds, the injection pump is shut off.

Step 2

- The system pump (

Sys Pmp) is turned on for 10 seconds.

Step 3

- The

Boiler contact is turned on for 10 seconds. After 10 seconds, the Boiler and Sys Pmp contacts are shut off.

Step 4

- After the test sequence is completed, the control resumes its normal operation.

Adjust Menu (2 of 2)

The system’s warm weather shut down during the
occupied (Day) period.

35 to 100

°F, OFF

(2 to 38

°C, OFF)

B3

Section

Advanced

Installer

Display

Description

Range

Actual

Setting

The system’s warm weather shut down during the
unoccupied (Night) period.

35 to 100

°F, OFF

(2 to 38

°C, OFF)

B3

The units of measure that all of the temperatures
are to be displayed in the control.

°F, °C

This item exits the ADJUST menu by pressing
either the or button.

Test

not testing

testing

testing paused

off

red

red

ADJUST

WWSD

°

F

OCC

ADJUST

WWSD

°

F

OCC

UN

ADJUST

°

F

ADJUST