Limited warranty and product return procedure, Technical data, Mixing control 361 variable speed – tekmar 361 Mixing Control User Manual

Page 20: 20 of 20

Advertising
background image

Limited Warranty The liability of tekmar Control Systems Ltd. and tekmar

Control Systems, Inc. (“tekmar”) under this warranty is limited. The purchaser,

by taking receipt of the tekmar product (“product”), acknowledges receipt of

the terms of the warranty and acknowledges that it has read and

understands same.

tekmar warrants each tekmar product against defects in workmanship and materi-
als, if the product is installed and used in compliance with tekmar's instructions. The
warranty period is for a period of twenty-four (24) months from the production date
if the product is not installed during that period, or twelve (12) months from the
documented date of installation if installed within twenty-four (24) months from the
production date.

The liability of tekmar under this warranty shall be limited to, at tekmar's sole dis-
cretion: the cost of parts and labor provided by tekmar to repair defects in materials
and/or workmanship of the defective product; or to the exchange of the defective
product for a replacement product; or to the granting of credit limited to the original
cost of the defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any way,
tekmar is not responsible, in contract, tort or strict product liability, for any
other losses, costs, expenses, inconveniences, or damages, whether direct, indi-
rect, special, secondary, incidental or consequential, arising from ownership or use
of the product, or from defects in workmanship or materials, including any liability
for fundamental breach of contract.

This warranty applies only to those products returned to tekmar during the

warranty period. This warranty does not cover the cost of the parts or labor

to remove or transport the defective product, or to reinstall the repaired or

Limited Warranty and Product Return Procedure

replacement product. Returned products that are not defective are not cov-
ered by this warranty.

This warranty does not apply if the product has been damaged by negligence
by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or

has been damaged by modifications, alterations or attachments made sub-

sequent to purchase which have not been authorized by tekmar; or if the
product was not installed in compliance with tekmar’s instructions and the

local codes and ordinances; or if due to defective installation of the product;
or if the product was not used in compliance with tekmar’s instructions.

This warranty is in lieu of all other warranties, express or implied, which the
Governing Law (being the law of British Columbia) allows parties to contrac-
tually exclude, including, without limitation, warranties of merchantability,
fitness for a particular purpose, durability or description of the product, its
non-infringement of any relevant patents or trademarks, and its compliance
with or non-violation of any applicable environmental, health or safety legis-
lation; the term of any other warranty not hereby contractually excluded is
limited such that it shall not extend beyond twenty-four (24) months from the
production date, to the extent that such limitation is allowed by the Govern-
ing Law.

Product Return Procedure Products that are believed to have defects in work-
manship or materials must be returned, together with a written description of the
defect, to the tekmar representative for that territory. If the address of the repre-
sentative is not known, please request it from tekmar at the telephone number
listed below

.

All specifications are subject to change without notice.

Printed in Canada. D 361 -

03/09.

Product design, software and literature are Copyright © 200

9 by:

tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.

Head Office: 5100 Silver Star Road

Vernon, B.C. Canada V1B 3K4

Tel. (250) 545-7749 Fax. (250) 545-0650

Web Site: www.tekmarcontrols.com

Control Systems

20 of 20

Technical Data

The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise.
Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian
Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception,
which is determined by turning the control off and on, the user is encouraged to try to correct the interference by reorienting or relocating
the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that
to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Caution The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and jumper

wires.
Attention Un boîtier nonmétallique n’assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de accord

spécialement conçus pour la mise á la terre.

• Press the Item, , buttons

simultaneously for 1 sec. to

enter the ADJUST menu

• Use the , buttons to

adjust the ROOM setting

To increase or decrease the

building temperature:

Mixing Control 361

Variable Speed

Mixing

Demand

50

30

10

C US

30% Enable

Return

10% Enable

Boiler Sensor

Supply

Installer

Advanced

ROOM - Set to desired room temp.

OUTDR DSGN - Set to coldest (design)

outdoor temp.

Installer Instructions

Terminal Unit Set to
High Mass Radiant

Low Mass Radiant

Fan Coil

Convector

Radiator

Baseboard

1

2

3

4

5

6

Refer to brochure for more information

Made in Canada by

tekmar Control Systems Ltd.
tektra 913-01

Power:

Variable Pump:

Relays:

Demand:

120 V +10% 50/60 Hz 1650 VA

240 V (ac) 2.4 A (FLA) 5 A (LRA), fuse T2.5 A

240 V (ac) 10 A 1/3 hp

20 to 260 V (ac) 2 VA

Signal wiring must be

rated at least 300V.

H1188D

MIX

°F

VIEW

Test

11 12 13 14 15 16 17

Do not apply power

UnO

Sw

Com Boil Mix Com Out Indr

9 10

Boiler

1

2

3

4

5

6

7

8

Mixing

Demand

L

N

Sys

Pmp N

Var

Pmp N

Power

Display defaults back to VIEW

menu after 20 sec.

% Out

Terminal

Unit

70 90

Item

OCC

Mixing Control 361 Variable Speed

Literature

— D 361, A 361’s, D 001, D 070, E 021.

Control

— Microprocessor PID control; This is not a safety (limit) control.

Packaged weight

— 3.0 lb. (1380 g), Enclosure A, blue PVC plastic

Dimensions

— 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)

Approvals

Ambient conditions

— Indoor use only, 32 to 102°F (0 to 39°C), < 90% RH non- condensing.

Power supply

— 120 V

±10%, 50/60 Hz, 1650 VA

Variable Pump

— 240 V (ac) 2.4 A (FLA) 5 A (LRA), fuse T2.5 A

Relays

— 240 V (ac) 10 A 1/3 hp

Demand

— 20 to 260 V (ac) 2 VA

Sensors included

— NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892

Outdoor Sensor 070 and 2 of Universal Sensor 0

82.

Optional devices

— tekmar type #: 032, 076, 077.

CSA C US, CSA 22.2 No 24 and UL 873, meets class B: ICES & FCC Part 15.

Meets Class B:

Canadian ICES

FCC Part 15

Dat

e Code

(ac)