Sequence of Operation

Section A

General Operation

Page 4-5

Section B

Mixing

Page 5-8

Section C

Boiler Operation

Page 8-9

Section A —General Operation

POWERING UP THE CONTROL

When the Mixing Control 361 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.

OPERATION

The 361 uses a variable speed injection pump to control the supply water temperature to a hydronic system. The supply water
temperature is based on either the current outdoor temperature, or a fixed setpoint.

Outdoor Reset

When the outdoor design (OUTDR DSGN) setting is not set to OFF, the
361 calculates a mixing supply temperature based on the outdoor air
temperature. The 361 uses a

Characterized Heating Curve and

optionally indoor temperature feedback from an indoor sensor in this
calculation.

Setpoint Control

When the outdoor design (OUTDR DSGN) setting is set to OFF, the
361 supplies a fixed mixing supply temperature equal to the MIX
TARGET setting. An outdoor sensor is not required during this mode
of operation.

VARIABLE SPEED

A standard wet rotor circulator is connected to the 361 on the

Var Pmp and N terminals (7

and 8). The 361 increases or decreases the power output to the circulator when there is a
mixing demand. The circulator speed varies to maintain the correct mixed supply water
temperature at the mix sensor. For correct sizing and piping of the variable speed driven
circulator, refer to essay E 021. A visual indication of the current variable speed output is
displayed in the LCD in the form of a horizontal bar graph.

BOILER PROTECTION (BOIL MIN)

The 361 is capable of providing boiler protection from cold mixing system
return water temperatures. If the boiler sensor temperature is cooler than
the BOIL MIN setting while the boiler is firing, the 361 reduces the output
to the variable speed injection pump. This limits the amount of cool return
water to the boiler, and allows the boiler temperature to recover. This
feature can only be used if a boiler sensor is installed.