DIP Switch Settings

The DIP Switch settings on the control are very important and should be
set to the appropriate settings prior to making any adjustments to the
control through the user interface. The DIP switch settings change the
items that are available to be viewed and / or adjusted in the user
interface.

ADVANCED / INSTALLER

The

Advanced / Installer DIP switch is used to select which items are available to be viewed and / or adjusted in the user interface.

30% ENABLE / 10% ENABLE

The position of the

30% Enable / 10 % Enable DIP switch determines at which pump output the control will close the Boiler contact under

normal conditions. This switch is only operational if the

Boiler Sensor DIP switch is set to Return. Refer to section C2.

BOILER SENSOR (RETURN / SUPPLY)

The

Boiler Sensor DIP switch selects the installation location for the boiler sensor. When the boiler sensor is installed on the supply side

of the boiler loop, the DIP switch must be set to

Supply. The boiler aquastat should be set at least 20°F (11°C) higher than the required

design boiler water temperature. The boiler is controlled as described in section C.

For systems where the 361 provides a heat demand to an external boiler control, the boiler sensor should be installed on the return side
of the boiler loop. When the boiler sensor is installed on the return side of the boiler loop, the DIP switch must be set to

Return. The 361

only enables the boiler when the output of the variable speed injection pump exceeds the boiler enable DIP switch setting. The

Boiler

contact is controlled as described in section C. The boiler’s operating temperature is controlled by its aquastat, or an external boiler reset
control.

Quick Setup

The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the

Advanced /

Installer DIP switch to Installer.

OUTDOOR RESET

Access the ADJUST menu by pressing and holding simultaneously for 1 second, all three buttons. The display will now show the word

ADJUST in the top right corner.

The ROOM OCC adjustment is the first item displayed. Use the or button to set the ROOM temperature.
The ROOM OCC setting is set to the desired room air temperature during the occupied (Day) mode.

Note: To increase or decrease space temperature during the occupied (Day) mode, only adjust the ROOM
OCC setting.

Press and release the

Item button to advance to the ROOM UNOCC adjustment. Use the or button to

set the desired temperature. The ROOM UNOCC setting is set to the desired room air temperature during
the unoccupied (Night) mode.

Note: To increase or decrease space temperature during the unoccupied (Night) mode, only adjust the
ROOM UNOCC setting.

Press and release the

Item button to advance to the OUTDR DSGN adjustment. Use the or button to

set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.

Press and release the

Item button to advance to the Terminal Unit adjustment. Use the or button to select

the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used.
The table below lists the terminal units and their default values.

ADJUST

ROOM

°

F

OCC

UN

ADJUST

DSGN

OUTDR

°

F

ADJUST

Terminal Unit

ADJUST

ROOM

°

F

OCC

30% Enable

Return

10% Enable

Boiler Sensor

Supply

Installer

Advanced

150°F (66°C)

170°F (77°C)

OFF

MIX DSGN

MIX MAX

MIX MIN

Terminal Unit

190°F (88°C)

210°F (99°C)

100°F (38°C)

High Mass Radiant

(1)

120°F (49°C)

140°F (60°C)

OFF

Low Mass Radiant

(2)

Fancoil

(3)

140°F (60°C)

160°F (71°C)

OFF

Fin-tube Convector

(4)

180°F (82°C)

200°F (93°C)

OFF

Radiator

(5)

160°F (71°C)

180°F (82°C)

OFF

Baseboard

(6)