View menu (1 of 1), Display description range – tekmar 361 Mixing Control User Manual

Page 15

Advertising
background image

Copyright © D 361 -

03/09

15 of 20

Press and release the

Item button to advance to the units adjustment. Use the or button to set the scale

to

°F or °C.

To exit the ADJUST menu, press and release the

Item button to advance to the ESC item. Then either press

the or button, or leave the buttons alone for 20 seconds.

SETPOINT CONTROL

Access the ADJUST menu by pressing and holding simultaneously for 1 second, the

Item, and buttons. The display will now show

the word ADJUST in the top right corner.

Press and release the

Item button to advance to the OUTDR DSGN adjustment. Press and hold the button

until OFF is displayed.

Press and release the

Item button to advance to the MIX TARGET adjustment. Use the or button to select

the desired temperature. The MIX TARGET setting is set to the desired setpoint supply temperature.

Press and release the

Item button to advance to the units adjustment. Use the or button to set the scale

to

°F or °C.

To exit the ADJUST menu, press and release the

Item button to advance to the ESC item. Then either press

the or button, or leave the buttons alone for 20 seconds.

Section

Advanced

Installer

View Menu (1 of 1)

Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
(OUTDR DSGN

OFF)

-67 to 149

°F

(-55 to 65

°C)

Display

Description

Range

Current room air temperature as measured by the indoor sensor.
(Indoor sensor is present)

23 to 113

°F

(-5 to 45

°C)

B1

Current mixed supply water temperature as measured by the
mixing sensor.

14 to 266

°F

(-10 to 130

°C)

B3

Target mixed supply is the temperature the control is currently
trying to maintain at the mixing sensor.

---, 14 to 266

°F

(---, -10 to 130

°C)

B1
B2
B3

Current boiler temperature as measured by the boiler sensor.
(Boiler sensor is present)

14 to 266

°F

(-10 to 130

°C)

ADJUST

°

F

ADJUST

DSGN

OUTDR

ADJUST

°

F

ADJUST

TARGET

MIX

°F

VIEW

MIX

°

F

OCC

VIEW

TARGET

MIX

°

F

OCC

VIEW

OUTDR

°

F

OCC

VIEW

ROOM

°

F

OCC

VIEW

BOIL

°

F

OCC

ADJUST

ADJUST

Advertising