Arcmaster, 300 s – Tweco 300 S Arcmaster User Manual

Page 20

Advertising
background image

ARCMASTER

®

300 S

March 31, 2006

3-2

1. Connect end of ground (YELLOW/GREEN) conductor to a suitable ground. Use a grounding method that complies with

all applicable electrical codes.

2. Connect ends of line 1 (BROWN) and line 2 (BLUE) and line 3 (RED) input conductors to a de-energized line disconnect

switch.

3. Use Table 1 and Table 2 as a guide to select line fuses for the disconnect switch.

NOTE

For Single-Phase operation connect the GREEN, BLACK and WHITE input conductors. Insolate the RED Conductor,
it is not used for Single-phase operation.

Input Voltage

Fuse Size

208

100

230

90

460

30

Table 1 Electrical Input Connections

NOTE

Fuse size is based on not more than 200 percent of the rated input amperage of the welding power source (Based
on Article 630, National Electrical Code).

Figure 3 - Electrical Input Connections

Advertising