Baumer BA Scatec10 15 User Manual
Page 22

User manual Scatec-10 / -15
22 / 44
Baumer Electric AG
Version 2011-03
www.baumer.com
Frauenfeld, Switzerland
is the intended tail edge
suppression zone
shorter than the dead path or
the distance run by the conveyor
within a dead time set in menu
C4, C6, or C8 ?
yes
is this intended zone
shorter than 2/3 of
the copy length ?
no
yes
no
invalid
configuration !
set
C10 or C11 Output pulse delay
to value
bigger than dead time
C4, C6, or C8
set
C9 Output pulse delay
to
1 = on
Edge will be suppressed if it is followed
by a gap in the lap stream
within the dead time or the dead path
set
C13 Tail edge suppression
to
0 = standard
set
C10 or C11 Output pulse delay
to value
equal to
the intended tail edge
suppression zone
set
C13 Tail edge suppression
to
1 = extended
Edge will be suppressed if it is followed
by a gap in the lap stream
within the output pulse delay
no
is
C1 Running direction
set to
0 = leading ?
yes
Retro-reflective foil
Laser beam
Overlap
Dead time
Copy length
Tail edge suppression zone
Interfering edges
Running direction