INSTALLATION REQUIREMENTS

The dryer must be connected to an exhaust outdoors.

Regularly inspect the outdoor exhaust opening and

remove any accumulation of lint around the outdoor

exhaust opening and in the surrounding area.

Exhaust system requirements, continued

Number of 90° turns

MAXIMUM LENGTH

of 4” (102mm) Rigid Metal Duct

VENT HOOD TYPE

(Preferred)

4”

(102mm)

louvered

2.5”

(6.35cm)

0

64 ft. (19.5 m)

48 ft. (14.6 m)

1

52 ft. (15.9 m)

40 ft. (12.2 m)

2

44 ft. (13.5 m)

32 ft. (9.8 m)

3

36 ft. (11 m)

24 ft. (7.3 m)

4

28 ft. (9.5 m)

16 ft. (4.9 m)

WARNING

FIRE HAZARD

A clothes dryer must be exhausted outdoors. Do not

exhaust dryer into a chimney, a wall, a ceiling, an attic,

a crawl space or any concealed space of a building. A

clothes dryer produces combustible lint. If the dryer is

not exhausted outdoors, some fi ne lint will be expelled

into the laundry area. An accumulation of lint in any

area of the home can create a health and fi re hazard.

WARNING

FIRE HAZARD

Exceeding the length of duct pipe or number of elbows

allowed in the “MAXIMUM LENGTH” charts can cause

an accumulation of lint in the exhaust system. Plugging

the system could create a fi re hazard, as well as

increase drying times.

WARNING

FIRE HAZARD

• Do not allow combustible materials (for example:

clothing, draperies/curtains, paper) to come in

contact with exhaust system. The dryer MUST NOT

be exhausted into a chimney, a wall, a ceiling,

or any concealed space of a building which can

accumulate lint, resulting in a fi re hazard.

• Do not screen the exhaust ends of the vent system,

or use any screws, rivets or other fasteners that

extend into the duct to assemble the exhaust

system. Lint can become caught in the screen, on

the screws or rivets, clogging the duct work and

creating a fi re hazard as well as increasing drying

times. Use an approved vent hood to terminate the

duct outdoors, and seal all joints with metal foil duct

tape. All male duct pipe fi ttings MUST be installed

downstream with the fl ow of air.

WARNING

FIRE HAZARD

• Do not install fl exible plastic or fl exible foil venting

material.

• If installing semi-rigid venting, do not exceed 8 ft.

(2.4 m) duct length.