Termination clearances – Vermont Casting 2996 User Manual

Page 11

Advertising
background image

11

Vermont Castings Pinnacle & Stardance Direct Vent - Rear Vent Gas Heaters

20003457

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

A =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

B =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

A

Balcony -
with no side wall

G =
Combustible&
Noncombustible
12"(305mm)

G

Balcony -
with perpendicular side wall

H = 24"(610mm)

J = 20"(508mm)

H

J

B

Recessed Location

C = Maximum depth of 48"
(1219mm) for recessed
location.

D = Minimum width for back wall
of a recessed location.
Combustible 38"(965mm)
Noncombustible 24"(610mm)

E = Clearance from corner in
recessed location.
Combustible 6"(152mm)
Noncombustible 2"(50mm)

C

D

C

E

V

V

Combustible &
Noncombustible

V

V

V

Fig. 10 Termination clearances.