Auto Mode

In the AUTO mode, the room temperature, set tempera-
ture, flame and fan levels will be shown. AUTO will
appear next to both the flame and fan icons.

When the control is in the AUTO mode, the main burner
will turn on/off or modulate based on the heat needed to
maintain the set temperature. The flame level will
change automatically to optimize the heat output
needed to maintain the set temperature. To change the
set temperature, press the up or down key. Pushing a
key once will change the temperature by one degree.

In the AUTO mode, the fan speed will increase with
increasing flame height or decrease with decreasing
flame height. “AUTO” is displayed next to the flame and
fan icons.

Fan Override During Auto Mode

If a lower or higher fan speed is desired when operating
in the AUTO mode, the fan speed can be overridden by
pushing the fan button followed by the up or down key.
Pushing a key once will change the fan level by one
unit. In this mode “AUTO” is displayed next to the flame
icon and “MANUAL” is displayed next to the fan icon.

Change Between F/C Temperature Units

Push the up and down arrow keys simultaneously for at
least 3 seconds to toggle between Fahrenheit and
Celsius units.

Disable Thermostat Function

To disable the thermostat function in the AUTO mode,
push the time and down keys simultaneously for at
least 3 seconds.

To Change Batteries

1. Remove cover on the backside of the transmitter.

Install 3 AAA batteries as shown and reattach cover.

2. Once steps 1-3 in OPERATION are completed,

receiver/valve and transmitter are now ready. Press
any button on transmitter for recognition process to
occur between the receiver/valve and transmitter.

3. Use functions as described in TRANSMITTER

section.

Troubleshooting

1. Locate LED light on valve.

2. LED will blink after every valid command received by

the transmitter; this is not an error.

3. Failure codes may occur anytime after pilot burner is

lit.

4. Sequence is failure code followed by light not

blinking for 30 seconds.

5. In the event of multiple failure codes, next failure

code follows previous failure code by approximately
3 seconds.

If an Error Code 3 is observed while performing the

testing, complete the following:

1. Make sure the spade connectors are pushed all the

way on. If rhe Error Code 3 is still showing, then go
to the next step.

2. Switch the front two thermopile leads with the back

two. Be sure the white lead is connected to the
spade with the white dot next to it. If the Error Code
3 is still showing, replace the thermopiles.

If an Error Code 8 is observed while performing the

testing, complete the following:

1. Confirm the valve is not in REMOTE mode.

• If the valve is producing Error Code 8 and in
REMOTE mode, the valve is defective and should
be replaced.

• If the valve is in LOCAL mode and producing Error
Code 8, then go to the next step.

2. Slide the Remote/Local switch to REMOTE and

teach the valve a transmitter (see item 6, page 1).
The Error Code will clear itself after approximately
1.5 minutes and return to normal operation.

LED Count Service Action

8

Replace valve

7

Confirm stepper motor connection exists

5

Confirm fan connection exists and works

4

Confirm gas type; jumper in place

3

Replace thermopiles

2

Turn fan ON

NOTE: Some keys are not active.

FAN

Antenna

Red

White

Red

White

Valve

(Bottom View)

Fan

Pilot

Assembly

FP1038

Fig. 67 Comfort Valve wiring diagram.

White Dots