Qmark QMKC Series - Electric Commercial Baseboard Heaters User Manual

Electric baseboard heaters, 2543nwc, Installation, operation & maintenance instructions

Advertising
background image

Electric Baseboard

Heaters

2500 & C2500 Series

WHEN USING ELECTRICAL APPLIANCES, BASIC PRECAU-
TIONS SHOULD ALWAYS BE FOLLOWED TO REDUCE
THE RISK OF FIRE, ELECTRIC SHOCK, AND INJURY TO
PERSONS, INCLUDING THE FOLLOWING:

1. Read all instructions before installing or using the heater.

2. A heater has hot and arcing or sparking parts inside, Do not

use in areas where gasoline or flammable liquids are used
or stored.

3. This heater is hot when in use. To avoid burns, do not let

bare skin touch hot surfaces. Keep combustible materials,
such as furniture, pillows, bedding, papers, clothes, and cur-
tains away from heater.

4. To prevent a possible fire, do not block air intakes or

exhaust in any manner.

5. Do not insert or allow foreign objects to enter any ventilation

or exhaust opening as this may cause an electric shock or
fire, or damage the heater.

6. Serious injury or death could result from electric shock.

Make sure electrical power supply circuit coming to heater
is disconnected at main disconnect or service panel before
installing or servicing this heater.

!

Installation, Operation & Maintenance Instructions

WARNING

GENERAL

This heater is designed to provide years of efficient, trouble free operation as a primary or supplementary heat source for comfort
heating in residential and commercial applications. Baseboard heaters must be thermostatically controlled for efficient, safe opera-
tion. A thermostat is not provided with this heater. However, a single or double pole thermostat accessory is available for installa-
tion into this heater at your place of purchase, or the heater may be connected to any suitable wall mounted thermostat that will
meet the electrical load requirements. Installation or use of this product in any manner not described herein will void the warranty
and could result in injury, damage to property, or permanent damage to heater.

IMPORTANT INSTRUCTIONS

MODEL NO.

2543NWC

1009

BASEBOARD HEATER
PLINTHE CHAUFFANTE
VOLTS AC

60HZ

WATTS

240/208

750/546

AMPS

3.1/2.7

54E1 LISTED

BASEBOARD HEATER

PATENT PENDING

4104-2109-265

MARLEY ENGINEERED PRODUCTS
BENNETTSVILLE, SC 29512

NAMEPLATE

DATE CODE

Figure 1: Nameplate Location

SAVE THESE INSTRUCTIONS

Table 2: Net Volumes of Wiring Compartment

CUBIC

CUBIC

DESCRIPTION

INCHES

CM

Heater Only (Each Wiring Compartment)

14.96

241

Heater W/SP Thermostat

11.18

180

Heater W/DP Thermostat

11.18

180

Heater W/Heat-Cool Switch Receptacle

9.51

153

Heater W/Duplex Receptacle

11.18

180

Heater W/DP Disconnect Switch

11.18

180

Heater W/Power Relay

10.76

174

Heater W/Transformer Relay

2.93

47

0 thru 12

12.1 thru 16
16.1 thru 24

15 amp
20 amp
30 amp

Total Amps

Minimum

AWG. Wire Size

(Copper)

Circuit Breaker

or Fuse Size

#14
#12
#10

Table 1

Advertising